The standard breaks down the calculation into two distinct stages: 1. The Adiabatic Basis

Preventing permanent damage to cable insulation during a fault. iec 949 pdf

While standard cable sizing focuses on continuous load carrying capacity, IEC 949 addresses the critical window—usually lasting less than five seconds—when a fault occurs and a massive surge of heat threatens to destroy cable insulation. Core Purpose of the Standard The standard breaks down the calculation into two

The adiabatic method assumes all heat generated by the short-circuit remains trapped within the conductor. This is a conservative "worst-case" scenario. Key Parameters: IADcap I sub cap A cap D end-sub : Permissible adiabatic short-circuit current (A). : Cross-sectional area of the conductor ( mm2m m squared : Duration of the short circuit (s). : Material-specific constant (e.g., 226 for copper). : Initial and final temperature limits (°C). 2. The Non-Adiabatic Modifying Factor Core Purpose of the Standard The adiabatic method